Description
CODE: | K400CL |
DESCRIPTION: | Surge protection for analog signals and logical , slim format . 6.2mm |
IEC CATEGORY / EN TYPE | C1, C2, C3, D1 |
RATED SURGE ARRESTER VOLTAGE UC | 25 VAC / 36 VDC |
LIGHTNING TEST CURRENT IIMP (10/350)ÎśS | 500 A |
NOMINAL CURRENT IN | 350 mA (40°C) |
NOMINAL DISCHARGE CURRENT IN (8/20)ÎśS | 10 kA |
RESIDUAL SURGE CURRENT (8/20)ÎśS LINE – GROUND | 20 kA |
OUTPUT VOLTAGE LIMITATIN AT 1 KV/ÎśS – LINE-LINE/LINE-GROUND | ≤ 60 V / ≤ 650 V |
MAX. BACK-UP FUSE (IN ACC. WITH IEC 127-2/III) | 315 mA |
RESISTANCE PER PATH | 3,3 Ω ± 20% |
TEMPERATURE RANGE | -40 °C … 80 °C |
DEGREE OF PROTECTION IN ACC. WITH CEI/EN 60539 | IP 20 |
INFLAMMABILITY CLASS IN ACC. WITH UL94 | V0 |
TEST STANDARDS | DIN EN 61643-21:2012 |
CONNECTION DATA (SOLID / STRANDED / AWG ) | 0,2-2,5 mm2 / 0,2-2,5 mm2 / 24-14 |
THREAD | M 3 |
TORQUE | 0,8 Nm |
STRIPPING LENGTH | 8 mm |
CONTAMINATION CLASS | 2 |
SURGE VOLTAGE CATEGORY | III |
MAX. INPUT VOLTAGE UI / UO | 36 V DC |
MAX.INPUT CURRENT II / IO (SEE ITEM 7) | T6: 150 mA / T5: 200 mA / T4: 350 mA |
MAX. INTERNAL CAPACITANCE CI / CO | 1,3 nF |
MAX. INNER INDUCTANCE LI / LO | 1 ÎĽH |
MAX. INNER POWER PI / PO | 3 W |
MAXIMUM INNER TIME FACTOR T (RI/LI) | 0,2 ÎĽs |