Description
POWER SUPPLY | 5..30 Vdc (loop powered) |
RESPONSE TIME | <220 ms (<620 ms with rejection 50-60 Hz) |
ACCURACY CLASS | 0,1% |
INPUT CHANNEL | • Pt100 Standard: EN 60751/A2 (ITS-90) Measuring range: -200..+650°C Minimum Span: 20°C 2,3,4-wire connection • Ni100 Measuring range: -60..+650°C Minimum Span: 20°C 2,3,4-wire connection |
OUTPUT CHANNEL | CURRENT (mA) 4..20, 20..4 mA (2-wire) |
THERMAL DRIFT | < 100 ppm (30 ppm tipical) |
PROGRAMMING | EASY SETUP software (programming kit: start / end of scale measurement, connection and RTD type, rejection, measurement filter, cable resistance, fault / over-range output) |
OPERATING TEMPERATURE | -40..+85°C |
CONNECTIONS | Spring clamps |
DIMENSION (ØXH) | Ø 43,7 x 20 mm |
STANDARD | CE |
NORMS | EN 61000-6-4, EN 61000-6-2 |