Description
Detachable clamps | Yes |
---|---|
Type of electric connection | Screw connection |
Model | Basic device |
---|---|
Suitable for monitoring of magnetic switches | Yes |
Suitable for monitoring of proximity switches | Yes |
Suitable for monitoring of emergency-stop circuits | Yes |
Suitable for monitoring of optoelectronic protection equipment | Yes |
Suitable for monitoring of position switches | Yes |
Enabling paths | Normally open contact |
---|---|
Signaling paths | Opener |
Contact material | Ag-alloy, gold-plated |
Rated switching voltage, enabling paths AC | 230Â V |
Rated switching voltage, enabling paths DC | 24Â V |
Max. thermal current Ith, enabling paths | 6Â A |
Max. thermal current Ith, signaling paths | 3Â A |
Max. total current I² of all current path | 9 A² |
Application category AC-15 (NO) | Ue 230V, Ie 3A |
Application category DC-13 (NO) | Ue 24V, Ie 2,5A |
Short-circuit protection (NO), max. fuse insert | 6 A class gG fuse, fuse integral < 100 A²s |
Mechanical life | 107Â switching cycles |
Outputs, signalling function, undelayed, with contact | 1 |
Outputs, safe, undelayed, with contact | 2 |
Input current (safety circuit / reset circuit) | 40Â mA |
---|---|
max. ​peak current (safety circuit / reset circuit) | 100 mA |
Response time tA1 | 40Â ms |
Response time tA2 | 500Â ms |
Min. switch-on time | 50Â ms |
Recovery time tW | >Â 40Â ms |
Release time tR | <Â 25Â ms |
Synchronous time tS | 200Â ms |
Permissable test pulse time tTP | <Â 1Â ms |
max. ​resistivity, per channel | ≤ (5 + (1,176 x UB / UN – 1) x 100) Ω |
Type of switch function of the inputs | Normally open contact |
Evaluation inputs | 2-channel |
Nominal voltage UN | AC/DC 24 V |
---|---|
Rated consumption AC | 4.4Â VA |
Rated consumption DC | 2Â W |
Rated frequency min. | 50Â Hz |
Rated frequency max. | 60Â Hz |
Operating voltage min. | 20.4Â V |
Operating voltage max. | 26.4Â V |
Electrical isolation supply circuit – control circuit | No |
Min. rated control supply voltage at AC 50 Hz | 20.4Â V |
Max. rated AC voltage for controls, 50 Hz | 26.4Â V |
Min. rated DC voltage for controls | 20.4Â V |
Max. rated DC voltage for controls | 26.4Â V |
Min. rated control supply voltage at DC | 20.4Â V |
Rated control supply voltage at AC 60HZ | 20.4Â V |
Rated control supply voltage at AC 50HZ | 26.4Â V |