Shop

Welcome to Swift Automation Stores

S400LV-1

Call for Price

SENECA Type 3 Surge Protection For Power Equipment, 24 Vac/Dc With 3 Conductors (L, N, PE)

Surge protection for single-phase, TN-S / TT ( SPD Class III , Type 3 ).

Description

CODE S400LV-1
DESCRIPTION Type 3 surge protection for power equipment
TEST CLASSIFICATION // EN TYPE III / T3
NUMBER OF PORTS One
NOMINAL VOLTAGE UN 24 V AC (TN-S)
NOMINAL FREQUENCY 50 Hz (60 Hz)
MAXIMUM CONTINUOUS OPERATING VOLTAGE UC 34 V AC / 34 V DC
COMBINATION WAVE UOC 2 kV
PROTECTION LEVEL UP – L-N / L-PE / N-PE ≤ 0,18 kV / ≤ 0,55 kV / ≤ 0,55 kV
RESIDUAL CURRENT IPE ≤ 5 μA
NOMINAL DISCHARGE CURRENT IN (8/20) ÎœS 1 kA
SHORT-CIRCUIT CURRENT RATING ISCCR 1,5 kA AC / 1 kA DC
RATED LOAD CURRENT IL AT 63 °C 16 A AC
MAX. BACKUP FUSE WITH BRANCH WIRING 16 A AC (B) / 10 A DC (gG) / 10 A DC (B)
MAXIMUM BACKUP FUSE FOR THROUGH WIRING 16 A AC (B) / 10 A DC (gG) / 10 A DC (B)
AMBIENT TEMPERATURE (OPERATION) -40 °C … 80 °C
DEGREE OF PROTECTION IP20

Additional information

Weight 0.105 kg

Download

Catalog – Surge Protections Devices – S400

Swift Automation Sdn Bhd | S400LV-1